Danfoss KP 61 Thermostat (060L110266) – −30 / +13 °C, SPDT, Automatic Reset, Remote Sensor with 2 m Capillary Tube
- Stock: In Stock
- Brand: Danfoss
- Model: 19.10.080
The Danfoss KP 61 (code 060L110266) is a remote-sensor thermostat that switches according to temperature in refrigeration and air conditioning installations. Its setting range is −30 … +13 °C; when the set value is reached, the contact changes over to switch the compressor, fan or heater on or off.
Remote Point Measurement: 2 m Capillary Tube + Ø9.5 × 70 mm Coil Sensor
This model’s sensor is type B: Ø9.5 × 70 mm remote air coil and is connected to the housing by a 2-meter capillary tube. This means that while the thermostat is mounted on a panel or wall, the measuring point can be 2 meters away: inside a cold room, at the evaporator outlet, in an air duct or inside a cabinet.
Do not confuse with the sister model: the KP 62 (060L110666) is from the same family, but its sensor is attached to the housing and has no capillary tube — it measures the air where the device sits. If you will measure a remote point, the KP 61 is the right choice; if you will measure the environment where the device is located, choose the KP 62.
Technical Specifications (Official Danfoss Data Sheet)
- Model: Danfoss KP 61 | Code: 060L110266 | Sensor Code: B
- Setting Range: −30 … +13 °C
- Differential (adjustable): 4.5 – 23 K at the low end of the setting range · 1.2 – 7 K at the high end
- Contact: SPDT (single pole, double throw) | Reset: Automatic
- Sensor: Ø9.5 × 70 mm remote air coil | Capillary tube: 2 m
- Charge Type: Vapour-charged thermal system
- Max. Sensor Temperature: 120 °C | Ambient Temperature: −40 … +65 °C
- Contact Load: AC1 16 A / 400 V · AC3 16 A / 400 V · AC15 10 A / 400 V · DC13 12 W / 220 V · LR 112 A
- Protection Class: IP30 (NEMA 1) | Cable Entry: Rubber gland, 6-14 mm cable
- Housing Dimensions: 84 × 61 × 44 mm | Net Weight: 0.366 kg — official dimension and sensor type drawing in the 2nd image
- EAN: 5702428014496
- 🔧 Place the sensor in the right spot. The coil sensor is placed at a point where the air whose temperature you want to control circulates freely. In front of a door, near a heat source or in a dead zone with no airflow gives false readings.
- ⚠️ Do not crush, sharply bend or shorten the capillary tube. The vapour charge inside it is the measurement itself; if the tube is damaged, the thermostat will not work and cannot be repaired. Coil any excess length in wide loops.
- Choose the differential to suit the job: a narrow differential keeps the temperature steady but cycles the compressor often; a wide differential reduces the number of starts and increases temperature swing.
- The SPDT contact can be used for both cooling (switch on when temperature rises) and heating (switch on when temperature falls) — wire according to the terminal diagram.
- IP30 is for indoor use; in wet or washed-down areas, place the housing inside an enclosure.
Loading...
Unlimited Blocks, Tabs or Accordions with any HTML content can be assigned to any individual product or to certain groups of products, like entire categories, brands, products with specific options, attributes, price range, etc. You can indicate any criteria via the advanced product assignment mechanism and only those products matching your criteria will display the modules.