Value VRP-15D Dual-Stage Vacuum Pump (420 L/min - 15 CFM, 5 Micron, R32 Compatible)
- Stock: In Stock
- Brand: Value
- Model: 46.01.286
This is the Value VRP-15D dual-stage vacuum pump, designed for deep and fast evacuation of air conditioning and refrigeration systems. Compatible with HFC and HFO refrigerants (e.g. R32), its non-sparking design allows safe use with new-generation flammable refrigerant classes. With its high flow rate of 420 L/min (15 CFM), it brings large-volume lines down to 5 micron in a short time.
High Flow, Deep Vacuum and R32 Safety
In installation and maintenance work where time and moisture control are critical in the field, you minimize workmanship errors with the VRP-15D's large oil sight glass, solenoid (electromagnetic) valve and gas ballast valve.
Key Technical Specifications and Equipment
- Dual-Stage Design: Reaches a final vacuum of 5 micron (0.067 Pa) with two-stage compression.
- Solenoid (Anti-Backflow) Valve: Holds the vacuum when the pump stops and prevents oil from flowing back into the system.
- Gas Ballast Valve: Prevents moisture from entering the pump oil, protecting oil life and vacuum quality.
- Non-Sparking Design: Safe use, compatible with A2L flammable refrigerants such as R32.
- High-Efficiency Oil Mist Filter: Reduces oil mist escaping from the exhaust and ensures clean operation.
- Large Oil Sight Glass: Oil level and condition can be seen clearly at a glance.
- Multiple Inlet Connections: 1/4 inch, 3/8 inch and 1/2 inch SAE — direct compatibility with different hoses and lines.
Technical Specifications
- Brand / Model: Value / VRP-15D (Dual-Stage, D Series)
- Flow Rate: 420 L/min (15 CFM)
- Ultimate Vacuum: 0.067 Pa (5 micron)
- Motor Power: 0.55 kW (0.75 HP)
- Number of Stages: 2 (dual stage)
- Power Supply: 230 V, 50-60 Hz
- Motor Speed: 2700 rpm (50 Hz)
- Inlet Connection: 1/4 inch, 3/8 inch, 1/2 inch SAE
- Oil Capacity: 0.88 L (mineral, viscosity 46 mm²/s)
- Noise Level: 63 dB
- Protection Class: IP44
- Operating Temperature: -1 / +40°C
- Dimensions: 414 x 152 x 310 mm
- Weight: 15.0 kg
- Cable Length: 200 cm
- Exhaust Plug: M30 x 1.5 mm
Technician Tips
- Before first start-up, check the oil level through the sight glass; do not run the pump if the oil temperature is below -1°C.
- On humid/long lines, use the gas ballast valve in the open position to prevent moisture from entering the oil; close it at the end of the process.
- For the fastest evacuation, use the 3/8 inch or 1/2 inch inlet together with a large-diameter vacuum hose (e.g. Value VHB Big Boy series).
Loading...
Unlimited Blocks, Tabs or Accordions with any HTML content can be assigned to any individual product or to certain groups of products, like entire categories, brands, products with specific options, attributes, price range, etc. You can indicate any criteria via the advanced product assignment mechanism and only those products matching your criteria will display the modules.
Also, any module can be selectively activated per device (desktop/tablet/phone), customer login status and other criteria. Imagine the possibilities.