Danfoss KP 62 Thermostat (060L110666) – −30 / +15 °C, SPDT, Automatic Reset, Ø40 mm Air Coil Sensor
- Stock: In Stock
- Brand: Danfoss
- Model: 19.10.090
The Danfoss KP 62 (code 060L110666) is a thermostat that switches according to air temperature in refrigeration and air conditioning installations. Its setting range is −30 … +15 °C; when the set temperature is exceeded or undershot, the contact changes over to switch the compressor, fan or heater on/off.
Control by Air Temperature: Sensor Attached to the Housing, No Capillary Tube
This model’s sensor is a type C1 Ø40 × 30 mm air coil and is attached directly to the bottom of the housing — it has no remote sensor or capillary tube. In other words, the device measures the air temperature where it is mounted. It is used by mounting directly inside a cold room, on a display cabinet body or at an air duct outlet.
If you need to measure a remote point (such as the evaporator outlet or product temperature), KP 61 models with capillary tube should be preferred; the KP 62 is not suitable for this job.
Technical Specifications (Official Danfoss Data Sheet)
- Model: Danfoss KP 62 | Code: 060L110666 | Sensor Code: C1
- Setting Range: −30 … +15 °C
- Differential: At max. range 1.5 – 7 K · at min. range 6 – 23 K (adjustable)
- Contact: SPDT (single pole, double throw) | Reset: Automatic
- Sensor: Ø40 × 30 mm air coil, attached to the housing — no capillary tube
- Charge Type: Vapour-charged thermal system
- Max. Sensor Temperature: 120 °C | Ambient Temperature: −40 … +65 °C
- Contact Load: AC1 16 A / 400 V · AC3 16 A / 400 V · AC15 10 A / 400 V · DC13 12 W / 220 V · LR 112 A
- Protection Class: IP30 | Cable Entry: Rubber gland, 6-14 mm cable
- Housing Dimensions: 84 × 61 × 44 mm | Weight: ≈0.4 kg — official dimension drawing in the 2nd image
- EAN: 5702428014533
- 🔧 The mounting location determines the measurement. Since the sensor is attached to the housing, the thermostat must be mounted where the air you want to measure is located. Above a door, near a heat source or in a dead-air zone gives false readings.
- Choose the differential to suit the job: A narrow differential (1.5-7 K) keeps the temperature steady but cycles the compressor often; a wide differential reduces the number of starts but increases temperature swing.
- ⚠️ SPDT contact: Can be used for both cooling (switch on when temperature rises) and heating (switch on when temperature falls) — wire according to the terminal diagram.
- IP30 is for indoor use; in wet/washed-down areas, place it inside an enclosure or use a model with higher protection.
- Do not cover the sensor coil — if air circulation is blocked, the thermostat responds with a delay.
Loading...
Unlimited Blocks, Tabs or Accordions with any HTML content can be assigned to any individual product or to certain groups of products, like entire categories, brands, products with specific options, attributes, price range, etc. You can indicate any criteria via the advanced product assignment mechanism and only those products matching your criteria will display the modules.