Danfoss TCHE 068U4582 Hot Gas Bypass (Capacity) Regulator – R407C, 10/12 mm ODF, 5.3 kW
- Stock: In Stock
- Brand: Danfoss
- Model: 18.35.342
Danfoss TCHE 068U4582 is a hot gas bypass (capacity) regulator for the refrigeration circuit. By diverting part of the hot gas in the compressor discharge line to the suction side in a controlled manner, it keeps the suction pressure constant; this prevents short cycling of the compressor and icing of the evaporator when the load drops.
Hot Gas Bypass Regulator for Capacity Control
⚠️ This product is not an expansion valve (TXV). An expansion valve feeds the evaporator from the liquid line and throttles according to superheat; a hot gas bypass regulator diverts gas from the discharge line to the suction line and reduces capacity at low load. The two products cannot be used interchangeably.
Typical applications: variable-load water chillers, process cooling, laboratory and medical refrigeration, and supermarket and air conditioning units that must run stably at low load. The regulator opens when the suction pressure drops below the set value and closes when the pressure rises.
Technical Specifications (Official Danfoss Data)
- Model: Danfoss TCHE | Code: 068U4582 (equivalent code: 068U4536)
- Type: Hot gas bypass / capacity regulator — externally equalized, one-way flow
- Refrigerant: R407C
- Setting Range: −1 °C … +8 °C (30 – 46 °F) evaporating equivalent
- Capacity: 5.3 kW (1.5 TR) | Orifice: No. 4
- Connections (ODF solder): Inlet 10 mm · Outlet 12 mm · Equalizer 6 mm
- Max. Working Pressure: 45.5 bar (660 psig)
- Capillary Tube: 900 mm
- Body: Stainless steel, angleway | Weight: 0.15 kg (valve net)
- Dimensions: Bulb Ø14.5 × 70 mm · body 35 mm · height 44 / 32 / 13 mm · inlet-outlet axes 38 + 38 mm — official dimensional drawing in the 2nd image
- Adjustment: Adjustable from the factory setting (≈2 °C superheat step)
- 🔧 Installation location: The regulator is connected so that it takes gas from the discharge line and injects it between the evaporator outlet and the TXV bulb; the equalizer line is taken from the suction tube.
- Liquid injection may be required: If hot gas is fed directly into the suction, the discharge temperature rises. For prolonged bypass operation, additional liquid injection should be planned to protect the compressor.
- Cool the body with a wet cloth during brazing; keep the flame away from the adjusting spindle and diaphragm area.
- Adjustment: The valve is expected to open when the suction pressure falls below the desired value; turn the adjusting screw in small steps and let the system stabilize.
Loading...
Unlimited Blocks, Tabs or Accordions with any HTML content can be assigned to any individual product or to certain groups of products, like entire categories, brands, products with specific options, attributes, price range, etc. You can indicate any criteria via the advanced product assignment mechanism and only those products matching your criteria will display the modules.