CEME CM-5925TE20D1W7 Solenoid Valve – 90° Angle Type, 1/4" ODF Solder, Normally Closed, Kv 0.120
- Stock: In Stock
- Brand: Ceme
- Model: CM-5925TE20D1W7
CEME CM-5925TE20D1W7 is a 2-way normally closed (NC) solenoid valve that opens and closes the liquid line electrically in refrigeration and air conditioning circuits. Thanks to its 90° angle body, the inlet connects from the side and the outlet from the bottom — eliminating the need for an elbow in tight lines. It has 1/4" ODF solder connections, an orifice diameter of Ø2.0 mm and a Kv value of 0.120 m³/h. The coil and connector are included with the product.
Opens and Closes the Liquid Line Electrically — Prevents Migration While the Compressor Is Off
The main task of a solenoid valve in the liquid line is to make a pump-down arrangement possible. When the thermostat reaches the set temperature, the valve closes, the compressor pumps the refrigerant out of the evaporator and stops on the low pressure switch. As a result, no liquid migrates into the evaporator during standstill; no liquid reaches the compressor at start-up, and the risk of leaks and oil dilution in the crankcase is reduced.
Normally closed (NC) means that the valve stays closed when the coil is de-energized. If the power fails, the line closes automatically — it is fail-safe. The body is brass and the internals are stainless steel; with a PTFE seal it operates down to −45 °C.
Technical Specifications (Official CEME Series 59 Document)
- Model: CEME CM-5925TE20D1W7 · Series 59
- Connection: 1/4" ODF solder, both ends the same size
- Orifice diameter: Ø2.0 mm · Kv: 0.120 m³/h
- Max. operating pressure differential (MOPD): AC 25 bar · DC 8 bar
- Working pressure: 0 – 28 bar
- Dimensions: A 59 · B 86.5 · C 40 mm
- Body: brass · internals stainless steel
- Seal: PTFE (optional neoprene)
- Medium temperature: −45 … +125 °C · ambient temperature: −30 … +80 °C
- Compatible refrigerants: all refrigerants — except ammonia (NH₃)
- Coil: 220-230 V AC 50/60 Hz · 13.5 VA · insulation class H (EN 60730)
- Electrical connection: 6.3 × 0.8 fast-on terminal · 3-pole connector, IP65 (DIN 43650A / UNI ISO 4400)
- Type: 2-way, normally closed (NC), direct acting
Box Contents
The valve body, coil, 3-pole connector and water/moisture protection kit come together. The mounting bracket is optional.
- 🔧 Flow direction is essential: The arrow on the body shows the flow direction. A solenoid valve fitted the wrong way round either does not open at all or does not close — check the arrow before installation.
- 🔧 Mounting position: Fit the valve on a horizontal tube with the coil facing upward. If the coil faces downward, the plunger does not seat by gravity and the valve malfunctions.
- ⚠️ Brazing warning: When brazing, always remove the coil and wrap the body in a wet cloth. The coil winding and internal seals are permanently damaged by excessive heat.
- ⚠️ Do not exceed the MOPD limit: For the valve to open, the pressure differential between inlet and outlet must be below 25 bar. At a higher pressure differential, the valve will not open even if the coil is energized.
- Installation location: In the liquid line, after the filter drier and before the expansion valve. If a sight glass is fitted ahead of it, you can see when the flow is shut off.
- The coil is continuously energized and feels hot to the touch; this is normal. With insulation class H, it withstands high winding temperatures.
Loading...
Unlimited Blocks, Tabs or Accordions with any HTML content can be assigned to any individual product or to certain groups of products, like entire categories, brands, products with specific options, attributes, price range, etc. You can indicate any criteria via the advanced product assignment mechanism and only those products matching your criteria will display the modules.
Also, any module can be selectively activated per device (desktop/tablet/phone), customer login status and other criteria. Imagine the possibilities.