Danfoss TE 2 Thermostatic Expansion Valve (068Z7486) – R454C, External Equalization, Flare Inlet × 12 mm Solder Outlet
- Stock: In Stock
- Brand: Danfoss
- Model: 19.70.216
Danfoss TE 2 (code 068Z7486) is an externally equalized thermostatic expansion valve (TXV) calibrated for R454C refrigerant. It continuously adjusts the amount of liquid entering the evaporator according to the suction line superheat; it keeps the evaporator fully fed while preventing liquid from reaching the compressor.
Calibrated for R454C: The Expansion Valve for Low-GWP A2L Refrigerants
R454C is a blend of R32 and R1234yf, a new-generation refrigerant with low global warming potential, GWP 148. It replaces R404A (GWP 3922) and R452A, which are restricted by the F-Gas regulation. It is in ASHRAE class A2L, meaning it is mildly flammable — it is subject to different rules from A1 refrigerants in terms of installation, ventilation and leak detection.
The thermostatic element is factory-charged to the R454C pressure-temperature curve; a valve made for R404A or R452A does not give the correct superheat in an R454C system. External equalization (TE 2) is mandatory on evaporators with a liquid distributor and on multi-circuit evaporators; it compensates for the pressure drop in the evaporator so that the valve opens correctly. The internally equalized T 2 model is only for single-circuit evaporators with low pressure drop.
Technical Specifications (Official Danfoss Data Sheet)
- Model: Danfoss TE 2 | Code: 068Z7486
- Type: Thermostatic expansion valve, externally equalized, with interchangeable orifice assembly
- Refrigerant: R454C (A2L, mildly flammable — GWP 148)
- Evaporating Range: −40 … +10 °C (Range N) | MOP: none
- Connections: Inlet flare × Outlet 12 mm ODF solder · Equalizer: 6 mm solder
- Max. Working Pressure: PS/MWP 34 bar | Test pressure PT 38 bar
- Temperature Limits: Min. −60 °C | Sensor max. 100 °C (with valve fitted), 60 °C (with element removed)
- Capillary Tube: 1.5 m | Sensor: Ø14.5 × 50 mm, clamp included
- Superheat: Static SS = 4 K (adjustable) · Opening OS = 6 K
- Body Dimensions: 35 + 54 mm width · 30 + 35 mm height · 34 mm depth | Weight: 0.3 kg — official dimension drawing in the 2nd image
Capacity — By Orifice Assembly (R454C)
The valve is sold as a body; the orifice assembly is separate; the orifice number determines the capacity. Rated values (te 4.4 °C / tc 38 °C):
- NO: 0X → 0.77 kW · NO: 00 → 1.5 kW · NO: 01 → 2.8 kW · NO: 02 → 3.6 kW
- NO: 03 → 6.2 kW · NO: 04 → 9.3 kW · NO: 05 → 11.8 kW · NO: 06 → 14.8 kW
- Total band: 0.77 – 14.8 kW. Orifice assemblies are available separately on our website.
- ⚠️ A2L refrigerant warning: R454C is mildly flammable. Carry out installation, leak testing and evacuation in accordance with A2L rules; do not neglect room ventilation and leak detection.
- 🔧 Take the equalizing line 15-20 cm after the sensor, from the top of the suction tube; a blocked line or one taken from the wrong point makes the valve open incorrectly.
- Clamp the sensor firmly to the suction tube at the 3-4 o'clock position and insulate it.
- Cool the body with a wet cloth while brazing and purge with nitrogen — the thermostatic element charge and the orifice filter are damaged by heat.
- Order the orifice assembly separately: If the NO matching your system capacity is not selected, the valve either lets liquid through or throttles and reduces capacity.
Loading...
Unlimited Blocks, Tabs or Accordions with any HTML content can be assigned to any individual product or to certain groups of products, like entire categories, brands, products with specific options, attributes, price range, etc. You can indicate any criteria via the advanced product assignment mechanism and only those products matching your criteria will display the modules.